Canbus Flow Sensor - Bronze

Highlights
• Suitable for use with sea water and with foam compounds
• Electromagnetic principle - No moving parts
• Canbus enabled or with high visibility backlit LCD readout
• Enables informed decisions
• 98% accurate
• Measures all firefighting flow rates
• Improves safety

Flow meters for harsh environments

A TSI flow meter adapted for use with foam compounds and in marine environments. The sensor casing is made from bronze to JIS standard BC6.

Available with either CanBus interface to J1939 for plug and play connection to any pump controller or with large digit LCD Readout

ALL TSI FLOW METERS FEATURE ELECTROMAGNETIC TECHNOLOGY. THE PROVEN TECHNOLOGY FOR FIRE SERVICES.

Not affected by turbulence in the water – can be installed directly onto pump manifold

No mechanical parts in water stream – not affected by any debris in the water and causes no pressure loss

Wide dynamic range – can measure the full range of fire-fighting flow rates with good accuracy

High reliability

Good accuracy. ±2% of measuring range (30 ~ 3,000 lpm)

Excellent Repeatability

 

Model No. 33-1020
General Range: 30 – 3,000 lpm
Resolution:   50 – 750 lpm: ± 15 lpm
> 750 lpm: ±2%
Supply Voltage: DC 8V ~ 32V (CanBus version)

                          DC 24V +20% / -10% (LCD readout version)

Negative Chassis Earth.
Supply Current: 0.35A
Operating Temp: -10 to +50ºC
Standard Functions: Flow reading.

SENSOR

Measurement Principle: Electromagnetic
Signal Output: CanBus to J1939 format
Casing Material: JIS BC6, bronze
Pressure rating: 24 bar
Protection level: IP65
Inner pipe diameter: 60 mm
Dimensions: Ø140 x 210 x 100 mm
Weight: 7.5kg
Adaptor: Matched to pipework. Contact TSI

Sensors.pdf (494.79 KB)
Know the Flow.pdf (2094.94 KB)